Showing 187 defects · Clear filters
Status
Open (105)Resolved (82)All (187)
Property
All (187)GH (31)KH (69)NH (87)
Severity
All (187)Critical (7)Major (41)Moderate (73)Minor (66)
RefPropertySeverityTitleStatusIdentifiedResolved
DEF-2026-0207KHMAJORL2 PS Office - Ceiling leakingopen2026-08-25—
DEF-2026-0206NHMODERATE4ft tube light level 1open2026-08-17—
DEF-2026-0140KHMAJORSewer waste easementopen2026-08-08—
DEF-2026-0139KHMAJORNeighbor grey water ingressopen2026-08-08—
DEF-2026-0138NHMAJORMango Tree Removalresolved2026-08-022026-08-18
DEF-2026-0137GHMODERATEDPP's office 24000BTU ACopen2026-07-30—
DEF-2026-0136NHMODERATEL2 Humans Rights Board roomopen2026-07-28—
DEF-2026-0135NHMODERATEL2 Humans Rights common office spaceopen2026-07-28—
DEF-2026-0134NHMODERATEL2 Manager Legal's officework ordered2026-07-27—
DEF-2026-0133NHMODERATEFenceopen2026-07-24—
DEF-2026-0120NHCRITICALThe Fire Detection/ Alarm System is not functioningopen2026-07-17—
DEF-2026-0117KHMODERATETube light fixtureopen2026-06-27—
DEF-2026-0116KHMODERATEMissing windowopen2026-06-27—
DEF-2026-0115KHMAJORLeaking toiletresolved2026-06-272026-07-06
DEF-2026-0114KHMAJORLeaking toiletresolved2026-06-272026-07-07
DEF-2026-0113GHMODERATEDPP's office windowopen2026-06-25—
DEF-2026-0112GHMODERATEGround floor lights in Livai's officeresolved2026-06-242026-07-07
DEF-2026-0111GHMINORMiddle floor men's washroom sinkopen2026-06-24—
DEF-2026-0110GHMODERATEMiddle floor lightsopen2026-06-24—
DEF-2026-0109GHMODERATETop floor kitchen lightsopen2026-06-24—
DEF-2026-0107GHMODERATELight in DPP Secretary's roomresolved2026-06-242026-07-07
DEF-2026-0106KHMAJORRoof leakresolved2026-06-162026-07-07
DEF-2026-0105NHMODERATEBulbs in ground floor reception need replacingresolved2026-06-022026-06-02
DEF-2026-0104KHMAJORWater leakopen2026-05-26—
DEF-2026-0029KHMINORWater meter keys - service or installopen2026-02-19—
DEF-2026-0031KHMINORV drain covers - installopen2026-02-19—
DEF-2026-0027KHMAJORWater tank - no non-return valvesopen2026-02-19—
DEF-2026-0028KHMODERATEInstall shut-off valves for handbasins + sinksopen2026-02-19—
DEF-2026-0030KHMODERATEAC drains not connected to downpipeopen2026-02-19—
DEF-2026-0016KHMINORL2 Male T1 - seat coverresolved2026-02-192026-02-19
DEF-2026-0015KHMINORL2 Kitchenette - tap fixingresolved2026-02-192026-02-19
DEF-2026-0014KHMINORL1 Female Handbasin - tapresolved2026-02-192026-02-19
DEF-2026-0013KHMODERATEL1 Female Toilet - cistern leakresolved2026-02-192026-02-19
DEF-2026-0012KHMODERATEL1 Female - floor wasteresolved2026-02-192026-02-19
DEF-2026-0011KHMODERATEL1 Female Shower - head + piperesolved2026-02-192026-02-19
DEF-2026-0010KHMODERATEL1 Male Handbasin - sink + tapresolved2026-02-192026-02-19
DEF-2026-0009KHMAJORL1 Male Urinal - blockageresolved2026-02-192026-02-19
DEF-2026-0008KHMAJORL1 Male T2 - pan connector leakresolved2026-02-192026-02-19
DEF-2026-0007KHMINORL1 Male T1 - cistern + seatresolved2026-02-192026-02-19
DEF-2026-0006KHMODERATEL1 Kitchen - tap + blockageresolved2026-02-192026-02-19
DEF-2026-0002KHMAJORG Male - toilet pan connectorresolved2026-02-192026-02-19
DEF-2026-0003KHMINORG Male - general worksresolved2026-02-192026-02-19
DEF-2026-0004KHMODERATEG Female - shower headresolved2026-02-192026-02-19
DEF-2026-0023KHMODERATEExternal - outdoor water piperesolved2026-02-192026-02-19
DEF-2026-0005KHMINORG Female - toilet seatresolved2026-02-192026-02-19
DEF-2026-0024KHMAJORExternal - meter leakresolved2026-02-192026-02-20
DEF-2026-0025KHMINORExternal V Drains - rubbishresolved2026-02-192026-02-20
DEF-2026-0026KHMINORExternal V Drains - clearingresolved2026-02-192026-02-20
DEF-2026-0022KHMINORL2 Female Handbasin - strainerresolved2026-02-192026-02-19
DEF-2026-0021KHMODERATEL2 Female T1 - pan + cisternresolved2026-02-192026-02-19
DEF-2026-0001KHMODERATEG Male - shower headresolved2026-02-192026-02-19
DEF-2026-0020KHMINORL2 Female T2 - seat + cisternresolved2026-02-192026-02-19
DEF-2026-0019KHMODERATEL2 Male Handbasin - tap + hoseresolved2026-02-192026-02-19
DEF-2026-0018KHMAJORL2 Male Urinal - blocked flushresolved2026-02-192026-02-19
DEF-2026-0017KHMAJORL2 Male T2 - pan connector leakresolved2026-02-192026-02-19
DEF-2026-0095NHMODERATEL2 Male — toilet leakresolved2026-02-132026-02-13
DEF-2026-0076NHMODERATEExternal — V drain & pipes clearedresolved2026-02-132026-02-13
DEF-2026-0077NHMINORExternal — V drain #2resolved2026-02-132026-02-13
DEF-2026-0078NHMINORExternal — V drain #3resolved2026-02-132026-02-13
DEF-2026-0079NHMINORExternal — downpipe bracketresolved2026-02-132026-02-13
DEF-2026-0080NHMAJORExternal — chamber coverresolved2026-02-132026-02-13
DEF-2026-0081NHMODERATEExternal — water meters leakresolved2026-02-132026-02-13
DEF-2026-0082NHMINORExternal — additional itemresolved2026-02-132026-02-13
DEF-2026-0083NHMODERATEExternal — driveway blocked drainresolved2026-02-132026-02-13
DEF-2026-0084NHMINORExternal — downpipe bracket #2resolved2026-02-132026-02-13
DEF-2026-0085NHMODERATEGF Kitchen — sink leakresolved2026-02-132026-02-13
DEF-2026-0086NHMINORGF unspecified itemresolved2026-02-132026-02-13
DEF-2026-0087NHMODERATEGF Mens — urinals clearedresolved2026-02-132026-02-13
DEF-2026-0088NHMINORGF Mens — washers / tapresolved2026-02-132026-02-13
DEF-2026-0089NHMODERATEGF Mens T1 — cistern floatresolved2026-02-132026-02-13
DEF-2026-0090NHMODERATEGF Ladies T2 — pan connectorresolved2026-02-132026-02-13
DEF-2026-0091NHMAJORL1 Male — urinals clearedresolved2026-02-132026-02-13
DEF-2026-0092NHMINORL1 Kitchen — washersresolved2026-02-132026-02-13
DEF-2026-0093NHMINORL1 Ladies T1 — seat connectorresolved2026-02-132026-02-13
DEF-2026-0094NHMINORL1 Ladies — service & cleanresolved2026-02-132026-02-13
DEF-2026-0096NHMODERATEL2 Male toilet — leak & seatresolved2026-02-132026-02-13
DEF-2026-0097NHMINORL2 Female — handbasin sealsresolved2026-02-132026-02-13
DEF-2026-0098NHMODERATEL2 — leaksresolved2026-02-132026-02-13
DEF-2026-0099NHMINORL2 Female — washersresolved2026-02-132026-02-13
DEF-2026-0100NHMINORL2 Male — floatresolved2026-02-132026-02-13
DEF-2026-0101NHMINORL2 Male T1 — serviceresolved2026-02-132026-02-13
DEF-2026-0102NHMODERATEL2 Male T2 — new cisternresolved2026-02-132026-02-13
DEF-2026-0103NHMINORL2 Kitchen — neck/sealresolved2026-02-132026-02-13
DEF-2026-0038NHMINORL1 troffer tubes #1-5resolved2025-11-262025-11-26
DEF-2026-0039NHMINORL1 troffer tubes #7-9resolved2025-11-262025-11-26
DEF-2026-0040NHMINORL1 troffer tubes #10-12resolved2025-11-262025-11-26
DEF-2026-0041NHMINORL1 troffer tube #13resolved2025-11-262025-11-26
DEF-2026-0042NHMINORL1 troffer tube #14resolved2025-11-262025-11-26
DEF-2026-0043NHMINORL1 troffer tubes #15-16resolved2025-11-262025-11-26
DEF-2026-0044NHMINORL1 troffer tube #17resolved2025-11-262025-11-26
DEF-2026-0036NHMODERATEL1 Female toilet GPO & lightresolved2025-11-262026-08-14
DEF-2026-0035NHMINORL1 Male toilet tube light defectiveresolved2025-11-262026-08-14
DEF-2026-0034NHMINORPassage way tube light defectiveresolved2025-11-262026-08-14
DEF-2026-0069NHCRITICALL2 server room GPOs overloadedopen2025-11-26—
DEF-2026-0068NHMINORL2 male toilet switchopen2025-11-26—
DEF-2026-0059NHMODERATEL2 test GPOs & remove redundant cablingopen2025-11-26—
DEF-2026-0058NHMAJORL2 Director's room GPOsopen2025-11-26—
DEF-2026-0055NHMODERATEL2 spare office GPOsopen2025-11-26—
DEF-2026-0032NHMAJORMSB inspection #1open2025-11-26—
DEF-2026-0033NHMAJORMSB inspection #2open2025-11-26—
DEF-2026-0075NHMODERATEL2 kitchen new IP-rated GPOopen2025-11-26—
DEF-2026-0045NHMINORL1 troffer tube #18resolved2025-11-262025-11-26
DEF-2026-0067NHMINORL2 male toilet lights defectiveresolved2025-11-262026-08-14
DEF-2026-0061NHMINORL2 tube lights defective #4resolved2025-11-262026-08-14
DEF-2026-0052NHMINORL2 tube light defective #3resolved2025-11-262026-08-14
DEF-2026-0050NHMINORL2 tube light defective #2resolved2025-11-262026-08-14
DEF-2026-0049NHMINORL2 tube lights defective #1resolved2025-11-262026-08-14
DEF-2026-0046NHMINORL1 reception downlightsresolved2025-11-262026-08-14
DEF-2026-0051NHMINORL2 check & test switchesopen2025-11-26—
DEF-2026-0048NHMODERATEL2 redundant electrical/telecom cablingopen2025-11-26—
DEF-2026-0047NHMAJORL2 Sub-board test/label/upgradeopen2025-11-26—
DEF-2026-0054NHMINORL2 GPOs — general check and test required across flooropen2025-11-26—
DEF-2026-0037NHMINORL1 troffer tube #6resolved2025-11-262025-11-26
DEF-2026-0194KHMODERATESome toilet pans crackedresolved2025-11-072026-02-18
DEF-2026-0125KHCRITICALFire alarm control panel not active — smoke sensors inactiveopen2025-11-07—
DEF-2026-0126KHCRITICALNo fire hoses or extinguishers on siteopen2025-11-07—
DEF-2026-0127KHMODERATENo visible fire evacuation plansopen2025-11-07—
DEF-2026-0128KHMAJORNo backup electrical system installedopen2025-11-07—
DEF-2026-0129KHMAJOREmergency lighting requires upgradingopen2025-11-07—
DEF-2026-0130KHMAJORBackup power and water connection not completed at siteopen2025-11-07—
DEF-2026-0181KHMODERATEOutdoor AC units on ground — vehicle damage riskopen2025-11-07—
DEF-2026-0182KHMODERATENo emergency muster point signageopen2025-11-07—
DEF-2026-0183KHMODERATEPedestrian areas blocked — temporary structures and discarded furnitureopen2025-11-07—
DEF-2026-0184KHMODERATEFence sections require new galvanised meshopen2025-11-07—
DEF-2026-0185KHMODERATEV-drains and vegetation removal requiredopen2025-11-07—
DEF-2026-0186KHMINORWall/slab joint cleaning to prevent growthopen2025-11-07—
DEF-2026-0187KHMODERATERoof gutters likely require cleaningopen2025-11-07—
DEF-2026-0188KHMAJORNon-compliant AC split-unit pipework penetrationsopen2025-11-07—
DEF-2026-0189KHCRITICALDetached storage structure blocks fire escapeopen2025-11-07—
DEF-2026-0190KHMODERATENon fire-rated partitions installedopen2025-11-07—
DEF-2026-0191KHMAJORNo visible exit or emergency evacuation signageopen2025-11-07—
DEF-2026-0192KHMINORSurface ducting throughoutopen2025-11-07—
DEF-2026-0193KHMODERATENo Disability accessopen2025-11-07—
DEF-2026-0195KHMAJORIncomplete plumbing works for backup water supplyopen2025-11-07—
DEF-2026-0196KHMAJORAt least one leaking toilet pan per floorresolved2025-11-072026-02-18
DEF-2026-0197KHMAJORGround floor under-sink waste lines constantly blockedresolved2025-11-072026-02-18
DEF-2026-0198KHMODERATEDownpipes, fixings, V-drains and downpipe drains — cleaningopen2025-11-07—
DEF-2026-0199KHMODERATEEstablish AC servicing and testing regimeopen2025-11-07—
DEF-2026-0200KHMODERATECompliant HVAC penetrations required on AC changeoutsopen2025-11-07—
DEF-2026-0201KHMINORRemove redundant AC unitsopen2025-11-07—
DEF-2026-0202KHMAJORMSB and sub-boards — RCD/load testing requiredopen2025-11-07—
DEF-2026-0203KHMINOROld fluorescent tube lighting — upgrade opportunityopen2025-11-07—
DEF-2026-0163GHMINORLandscaping — minor drain cleaning and clearingopen2025-11-04—
DEF-2026-0164GHMAJORRecurring sewer manhole overflow during heavy rainopen2025-11-04—
DEF-2026-0165GHMODERATERoof gutters likely require cleaningopen2025-11-04—
DEF-2026-0166GHMINORExternal surfaces — rust stains and mould cleaningopen2025-11-04—
DEF-2026-0167GHMODERATERotting external timber cladding at lobby/waiting areaopen2025-11-04—
DEF-2026-0168GHMINORBlanking plate for old access control penetrationopen2025-11-04—
DEF-2026-0169GHMINORTimber stairs — sand and re-glaze refurbishmentopen2025-11-04—
DEF-2026-0170GHMODERATENon-slip strips on stair treads (tenant request)open2025-11-04—
DEF-2026-0171GHMINORWater supply pressure testing recommendedopen2025-11-04—
DEF-2026-0172GHMAJORSewer line overflow at entryopen2025-11-04—
DEF-2026-0173GHMODERATEEstablish AC servicing and testing regimeopen2025-11-04—
DEF-2026-0174GHMINORRemove redundant AC unitsopen2025-11-04—
DEF-2026-0175GHMODERATEHVAC testing/balancing/controls in PM regimeopen2025-11-04—
DEF-2026-0176GHMINORChimneys and vents follow-up auditopen2025-11-04—
DEF-2026-0177GHMAJORMSB and sub-boards — RCD/load testing requiredopen2025-11-04—
DEF-2026-0178GHMAJORGround-floor tea room GPO constantly trippingopen2025-11-04—
DEF-2026-0179GHMODERATEIP65 GPO required for hot water unit in staff bathroomopen2025-11-04—
DEF-2026-0180GHMINOROld fluorescent/CFL lighting — upgrade opportunityopen2025-11-04—
DEF-2026-0204NHMAJORBackup generator not installed — per tenancy agreementopen2025-11-04—
DEF-2026-0205NHMAJORBackup water supply connection/installation not completedopen2025-11-04—
DEF-2026-0122GHMODERATEFire extinguishers and hoses require servicing auditopen2025-11-04—
DEF-2026-0123GHMINORFire evacuation plan drawings fadedopen2025-11-04—
DEF-2026-0121GHCRITICALFire alarm control panel not activeopen2025-11-04—
DEF-2026-0124GHMODERATEBackup generator follow-up audit requiredopen2025-11-04—
DEF-2026-0141NHMAJORDriveway chamber cover requires replacementopen2025-11-04—
DEF-2026-0142NHMODERATENo emergency muster point signageopen2025-11-04—
DEF-2026-0143NHMODERATEPedestrian access blocked — discarded material on siteopen2025-11-04—
DEF-2026-0144NHMINORWall/slab joint cleaning to prevent growthopen2025-11-04—
DEF-2026-0146NHMODERATEMain roof gutters require cleaningopen2025-11-04—
DEF-2026-0147NHMINORConcrete window sills require cleaningopen2025-11-04—
DEF-2026-0148NHMINORInterior finishes tired — wet area tiles and ceilingsopen2025-11-04—
DEF-2026-0149NHMINORKitchenette cabinets need updating and expansionopen2025-11-04—
DEF-2026-0150NHMAJORNo visible exit signs or emergency evacuation signageopen2025-11-04—
DEF-2026-0145NHCRITICALElevator — shaft, well and full conveyance inspection requiredopen2025-11-04—
DEF-2026-0152NHMODERATEAdditional sanitary facilities with Disability accessopen2025-11-04—
DEF-2026-0153NHMINORNo sanitary bins or sanitary services provider engagedopen2025-11-04—
DEF-2026-0154NHMODERATEStormwater drains require checking and clearingopen2025-11-04—
DEF-2026-0155NHMODERATEEstablish AC servicing and testing regimeopen2025-11-04—
DEF-2026-0156NHMODERATECompliant HVAC penetrations requiredopen2025-11-04—
DEF-2026-0157NHMAJORFire alarm control panel not installed — manual call points onlyopen2025-11-04—
DEF-2026-0158NHMODERATENo visible fire evacuation route plansopen2025-11-04—
DEF-2026-0159NHMAJORElectrical and telecom closets — rubbish/cleaning items stored — OHS/fire riskopen2025-11-04—
DEF-2026-0160NHMODERATELightning protection requires licensed electrical inspectionopen2025-11-04—
DEF-2026-0161GHMAJORDriveway pavement damage — FRA responsibilityopen2025-11-04—
DEF-2026-0162GHMODERATEBackup water supply — sub-standard installationopen2025-11-04—